Fire Protection in the State Building Codes: How to Plan Transparent Architecture with Legal Certainty

Brandschutz in den Landesbauordnungen: Strategien für die rechtssichere Planung transparenter Architektur

Transparent facades, open atriums and light-filled escape routes are part of today's architectural standard. What the design gains in openness, however, the building authority assesses as a potential fire load and hazard zone. Fire protection in Germany is therefore not an optional extra but is bindingly regulated by the state building codes (Landesbauordnungen, LBO) of the 16 federal states.

The reason for the complexity is federalism: fire behaves the same way physically everywhere, yet the legal requirements for components such as fire-rated glazing often differ in detail between North Rhine-Westphalia, Bavaria or Berlin. Planners, architects and investors who are unaware of these differences risk costly redesigns, delays during approval – or, in the worst case, liability in the event of damage.

The Legal Framework: From the Model Building Code to the State Building Code

The Model Building Code (Musterbauordnung, MBO) only provides the framework. Issued by the Conference of Building Ministers, it has no legal force of its own but serves the 16 states as a template for their respective state building code.

Why differences exist at all

Every federal state may adapt the MBO to its regional needs. The BauO NRW, for instance, often sets stricter fire-protection requirements for densely built-up urban areas, while the BayBO (Bavarian Building Code) has recently simplified timber construction in particular and thereby deviated from the MBO.

For planning this means: the decisive code is always the LBO of the state in which construction takes place. Added to this are the relevant special-building ordinances – for example for assembly venues, hospitals or retail premises – which in many cases further tighten or specify the LBO requirements.

Building Classes 1 to 5 – the Starting Point of Planning

  • GK 1 & 2: Detached residential buildings or small units up to 7 m in height; interior fire-protection requirements remain moderate. Fire-rated glass usually only comes into play at property boundaries or in special boiler rooms.
  • GK 3: Buildings up to 7 m in height with more than two usage units. The LBO frequently requires fire-retardant components (30 minutes). Transparent partitions in corridors must then already comply with the fire-protection standard – for example with ARDOREX® Arnold Fire in class EI 30, which as laminated glass achieves up to 86 % light transmission (Source: ARDOREX® data sheet, as of 11/2024).
  • GK 4: Buildings up to 13 m in height with usage units up to 400 m². The requirement rises to highly fire-retardant (60 minutes). At this critical threshold, the choice between E 60 (pure integrity) and EI 60 (with insulation) often has to be made. ARDOREX® Arnold Fire EI 60.18, with a Ug value of 4.6 W/(m²K) in laminated glass, has proven itself here.
  • GK 5 & special buildings: Buildings over 13 m in height or those of special type and use; here, fire-resistant (90 minutes) generally applies. In the stairwells of these classes, transparent planning is barely feasible without high-performance fire-rated glass (EI 90). ARDOREX® Arnold Fire EI 90.24 reaches this class at up to 84 % light transmission.

What the LBO Protects: Three Central Objectives

  1. Preventing the outbreak of fire: Glass plays a minor role here because it is classified as a non-combustible building material (A1/A2 according to DIN 4102).
  2. Limiting the spread of fire: This is where fire-rated glazing comes into play. It is intended to prevent fire from crossing from one fire compartment into the next (fire walls, partition walls).
  3. Rescuing people and animals: the most critical objective. Escape routes – necessary corridors and stairwells – must remain free of smoke for a defined period and provide protection from radiant heat. This is exactly where ARDOREX® excels: the hydrogel layer keeps the temperature on the cold side, on average, to less than a 140 K increase above the initial temperature.

E, EW and EI: the European Classification in Detail

To implement the LBO requirements correctly, planners must have a firm command of the classification according to DIN EN 13501-2.

E (Integrity) – room closure

Historically referred to as G-glass. Such glazing only holds back flames and smoke; the dangerous heat radiation passes through almost unhindered. According to the LBO, it is only permitted where there are no combustible materials nearby and no one is directly endangered – for example in skylights or partitions without escape-route relevance.

EW (Radiation) – radiation limitation

An intermediate step that is rarely explicitly required in the German LBOs but is often used as compensation. EW glass keeps radiant heat below 15 kW/m² at a distance of one metre.

EI (Insulation) – thermal insulation

Referred to nationally as F-glass and the highest fire-protection standard. EI glass provides comprehensive protection against flames, smoke and heat; on the side facing away from the fire, the pane may heat up by an average of no more than 140 K above the initial temperature. ARDOREX® Arnold Fire covers classes EI 30 to EI 120 (Source: ARDOREX® data sheet, as of 11/2024). According to the LBO, EI is mandatory for all glazing in necessary corridors and stairwells – to safeguard evacuation.

Brandschutz in den Landesbauordnungen: So planen Sie transparente Architektur rechtssicher

Fire-Rated Glass in Practice: Typical Installation Situations

Necessary corridors and stairwells

The LBO regards them as the building's life insurance. Walls of necessary corridors must generally be fire-retardant (GK 3) or highly fire-retardant (GK 4/5). Anyone who wants to open them up to bring daylight into the corridors must design the glazing in the same class as the wall. In the advance variant, ARDOREX® Arnold Fire offers a clear advantage here: as double insulating glass it achieves a Ug value of 1.1 W/(m²K) and thus meets the Building Energy Act (GEG) requirements alongside fire protection (Source: ARDOREX® data sheet, as of 11/2024).

Practical tip: Frameless fire-rated glazing (butt-joint systems) can visually widen corridors without violating the EI requirements of the LBO.

Fire protection at the property boundary (fire wall)

If a building stands directly on the property boundary, the LBO requires a fire wall. Openings in it are generally prohibited. Exceptions allow fixed fire-rated glazing, provided it meets class EI 90 (fire-resistant) and cannot be opened. In dense urban development this is often the only way to bring daylight into rooms close to the boundary. ARDOREX® Arnold Fire EI 90.24 in a laminated-glass build-up provides a solution with a thickness of just 50 mm and a weight from 54 kg/m².

Facade fire spread and fire barriers

With large-area glass facades there is a risk of fire spreading from one storey into the storey above from the outside. The LBO therefore frequently requires fire barriers of at least 1 m in height made of non-combustible materials – or corresponding fire-rated glazing in this area. For use in exterior walls, ARDOREX® is CE-certified according to EN 16034 and EN 14351-1 (Source: ARDOREX® data sheet, as of 11/2024).

Not Just the Pane: the Tested Overall System Is Decisive

A common mistake in practice is to consider the glass pane alone. The LBO, however, requires the proof of usability for the complete component.

The system approach

Fire-rated glass works only in interaction with the tested frame profile (steel, aluminium, wood, plasterboard or lightweight partition), the matching glass holders and seals, and professional installation in the structure. ARDOREX® Arnold Fire is tested and approved in metal, wood and gypsum systems. The relevant general construction-type approvals include Z-19.14-1833, Z-19.14-2118, Z-19.14-1993 and Z-19.14-2652 (Source: ARDOREX® data sheet, as of 11/2024).

Verifications: abZ and aBG

Every fire-rated glazing needs a building-authority proof of usability. In Germany this is usually the general building-authority approval (abZ) or the general construction-type approval (aBG). Even small deviations from the approval – such as larger pane dimensions – cause it to lapse. A project-specific construction-type approval (vBG) must then, for example, be applied for at the highest building supervisory authority. Arnold Glas supports planners with the necessary verifications and expert reports as early as service phase 2.

Cost-Effectiveness: More Than Pure Fire Protection

  • Multifunctionality: ARDOREX® advance combines fire protection with thermal insulation (Ug down to 0.5 W/(m²K) in a triple insulating-glass build-up) and sound insulation (Rw up to 46 dB in laminated glass, F90). An additional secondary shell can thus be omitted (Source: ARDOREX® data sheet, as of 11/2024).
  • Insurance advantages: High-quality fire-protection concepts can have a positive effect on insurance terms in industrial and commercial construction.
  • Durability: Thanks to a UV-resistant interlayer without additional UV protective film, the glazing retains its transparency throughout its entire life cycle (Source: ARDOREX® product brochure).
  • Colour rendering: With an Ra value of up to 98 (laminated glass), ARDOREX® is almost colour-neutral – a plus for architecturally demanding projects (Source: ARDOREX® data sheet, as of 11/2024).

ARDOREX® advance: Fire Protection and the Building Energy Act Combined

With the advance range, Arnold Glas answers the rising requirements for summer and winter thermal protection while maintaining fire protection at the same time. Whereas the classic laminated glasses (EI 30 to EI 120) are intended mainly for interior fit-out, the advance line targets facades and exterior walls specifically.

The key technical data at a glance (Source: ARDOREX® data sheet, as of 11/2024):

Build-up

Class

Ug W/(m²K)

Light trans.

Weight

Double glazing (ISO)

EI 30

1.1

77 %

approx. 55 kg/m²

Double glazing (ISO)

EI 60

1.1

77 %

approx. 61 kg/m²

Double glazing (ISO)

EI 90

1.1

76 %

approx. 74 kg/m²

Triple glazing (ISO)

EI 30

0.7

70 %

approx. 65 kg/m²

Triple glazing (ISO)

EI 60

0.7

69 %

approx. 71 kg/m²

Triple glazing (ISO)

EI 90

0.7

69 %

approx. 77 kg/m²

Note: In the double build-up, Ug values down to 1.0 W/(m²K) are possible, and in the triple build-up down to 0.5 W/(m²K).

Decisive: the low Ug value in the triple build-up meets the minimum energy requirements of the GEG without a separate thermal-insulation layer being required. Sound-insulation values are tested and specified exclusively for the laminated (mono) build-up; the entire component must be measured individually on site.

Designing Safely with a System

  • Determine the building class according to the LBO.
  • Clarify the protection objectives of the affected walls (partition wall or fire wall).
  • Define the EI classification for escape routes.
  • Check approval ranges – dimensions and frames – at an early stage.
  • Involve Arnold Glas consulting from service phase 2 – for verifications, vBG support and system advice.

These Topics Might Also Interest You

What the classes E, EW and EI specifically mean is explained in our article Fire Resistance Classes E, EW and EI: Meaning, Differences and Requirements.

How fire protection and smoke control differ is covered in Fire-Resistant Glass vs. Smoke-Control Glass: Why the Distinction Decides Safety.

All application areas and system variants can be found on our Fire Rated product page.

Frequently Asked Questions on Fire Protection in the LBO

May I cut fire-rated glass myself?

No. Each pane is manufactured to size and sealed at the factory. Subsequent cutting destroys the hydrogel layer and causes the approval to lapse.

Is there fire-rated glass in curved form?

Yes, technically feasible – but usually only via a project-specific construction-type approval (vBG), as standard approvals generally cover only flat panes.

Is wired glass sufficient as fire protection?

Under today's LBO, usually no longer. Wired glass often only reaches class E (integrity) and is not safety glass (risk of injury). It rarely meets current requirements for escape routes.

How do I recognise installed fire-rated glass?

By its permanent marking: a stamp in one corner states the manufacturer, type and classification (e.g. EI 30).

What is a fire-protection concept?

For special buildings, the LBO requires a holistic fire-protection concept, prepared by a certified expert. Deviations from the LBO are also defined and compensated for within it.

Can wooden frames be used in fire protection?

Yes. ARDOREX® is tested and approved in constructions made of hardwood and softwood – as a muntin wall for interior use or as a ribbon window for exterior use. Systems with wooden profiles reach up to EI 90 (Source: ARDOREX® product brochure).

Author: Arnold Glas Marketing Department

Arnold Zentralverwaltungsgesellschaft mbH
Alfred-Klingele-Str. 15
73630 Remshalden
Routenplaner (www)